Age | Commit message (Collapse) | Author | Files | Lines |
|
1. add acpi-power-state daemon to check the ACPI power
states from BIOS
2. set failsafe fan speed at different states
- S0_G0_D0: 90%
- S5_G2: 40%
Note:
this item depends on the commit and will
add as the patches first in another PR
https://gerrit.openbmc-project.xyz/38112
3. add gbs-check-host-state.sh to monitor the power state
D-Bus and then trigger to set fan failsafe speed
4. remove gbs-detect-fan-fail service and unused scripts
from phosphor-pid-control
5. update read-margin-temp srcrev to avoid nvme temperature
sensor failed due to nvme SSD not-present
Signed-off-by: George Hung <george.hung@quantatw.com>
Change-Id: I496dd7bc59076a2b3690e367877d49533855c9fe
|
|
Change the sensor name of fans:
fan2 -> fb_fan0
fan3 -> fb_fan1
fan4 -> fb_fan2
(From meta-quanta rev: 43bbb292c0d151841db415802849df965f6151ce)
Signed-off-by: George Hung <george.hung@quantatw.com>
Change-Id: If81cf92c50da512986344b31ba20d93af6dcf061
Signed-off-by: Andrew Geissler <geissonator@yahoo.com>
|
|
When detecting fan fail, set other fans full speed
(From meta-quanta rev: fe75a9e492d94088d5d70b9cf5bce24e47898b2f)
Signed-off-by: George Hung <george.hung@quantatw.com>
Change-Id: I764c9d90f551475de773dfc563763112127bde73
Signed-off-by: Andrew Geissler <geissonator@yahoo.com>
|