wspoon: Enable fan control to run at BMC standby
To allow thermal modes to be selected at BMC standby, the fan control application must be running. The phosphor-fan-control@.service file is needed to start fan control at BMC standby and the phosphor-fan-control-init@.service is no longer required. Tested: Witherspoon phosphor-fan-control@.service replaced in image phosphor-fan-control-init@.service removed from image fan watchdog configs appended to fan control service still phosphor-fan-control@.service started at BMC standby fan control thermal modes presented/changeable at BMC standby no function change in configured thermal modes (From meta-ibm rev: f59761e1af85b3ae6432bf0297f5cfe5be71e557) Change-Id: I4a946f58b6f0c22ebd402304ae9d8fd17a197571 Signed-off-by: Matthew Barth <msbarth@us.ibm.com> Signed-off-by: Brad Bishop <bradleyb@fuzziesquirrel.com>